The licensee notified the NRC Resident Inspector and will notify the State of
Delaware.
To top of pagePower Reactor Event Number: 45848
Facility: SALEM
Region: 1 State: NJ
Unit: [1] [ ] [ ]
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MATT MOG
HQ OPS Officer: HOWIE CROUCH Notification Date: 04/16/2010
Notification Time: 22:08 [ET]
Event Date: 04/16/2010
Event Time: 16:41 [EDT]
Last Update Date: 04/16/2010
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
MEL GRAY (R1DO)
Unit SCRAM Code RX CRIT Initial PWR Initial RX
Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text UNPLANNED EMERGENCY DIESEL GENERATOR START DUE TO LOSS OF A 4160 V
BUS
"At 1641 hours [EDT] on April 16, 2010, an [unplanned] automatic start signal
was generated for the 1C Emergency Diesel Generator (EDG). Surveillance testing
was being performed on the 1C 4160 volt bus to verify the ability to swap
between the 13 and 14 Station Power Transformers (SPT) which are the offsite
power in-feeds for the 1C 4160 volt bus. The [failure to] swap from the 13 SPT
to 14 SPT resulted in a loss of power to the 1C 4160 volt vital bus generating
the automatic start signal for the 1C EDG. The 1C EDG started but the output
breaker did not close. Abnormal operating procedure S1.OP-AB.4KV-0003 was
entered for loss of the 1C 4160 volt vital bus. Salem Unit 1 was in Mode 6 with
core reload (fuel movement) in progress. Fuel movement was stopped as a result
of the loss of the 1C 4160 volt bus. All fuel assemblies were placed in a safe
position. There was no impact to shutdown cooling and no loss of spent fuel pool
cooling. Core reload has been suspended until power is restored to the 1C 4160
volt bus. Initial investigations determined the suspected cause to be a failed
auxiliary contact associated with a SPT in-feed breaker. This prevented the
opposite in-feed and EDG breaker from closing. Extent of condition review and
repairs are in progress."
Fuel movement was suspended due to loss of the fuel handling building exhaust
fan which is powered by the 1C 4160V bus. There was no further impact on any
safety related equipment required in Mode 6.
The license will notify the NRC Resident Inspector, Lower Alloways Creek
Township, the State of New Jersey, and the State of Delaware.